Products
 
 
 
 
 
Product Datasheets

8576B - µGauge

Model 8576B µGauge

Features

Unique display shows both analog and digital values simultaneously; shows setpoint position and condition

Dual switch outputs

4-20 mA output signal standard for 4-20 mA input model; second 4-20 mA output signal optional

4-20 mA output signal optional for 1-5 Vdc input model

Two protected adjustable set points - independently configured as rising or falling

4 1 / 2 digit n 101 segment bar graph with setpoint indication - linear or differential

Menu driven software configuration (no external programming device required)

Benefits

Universal 4-20 mA / 1-5 Vdc input measures virtually any type of process function

4-20 mA output allows signal to be carried through to other measuring/control equipment

Software allows gauge to be utilized for various applications

Bargraph provides operator with vital information "at a glance"

Fiber-optic backlighting provides consistent illumination under low-light conditions

Retrofits into existing gauge cutouts

Setpoint hysteresis for noisy signals

Setpoint viewing without disturbing monitoring

Operation

AMOT Model 8576B µGauge is an electronic panel meter suitable for use in hazardous environments. The 8576B displays any single process variable in a digital and analog format. As well as the dual display, the µGauge has 2 user configurable discrete outputs, and an additional 4-20mA output for retransmission of the process pressure to other equipment. The 8576B is designed to retrofit into an existing gauge hole and will accept inputs from any 1-5 Vdc or 4-20 m transmitter. The µGauge is completely configurable from the front panel. The user has the ability to change the following parameters: Setpoints, Calibration, Averaging, Output Modes, Bar Graph, Range, Decimal Point Position, Least Significant Digit, Hysteresis, and Sensor Fail Action.

Specifications

Area Classification:
Area: Class 1, Division 2 Group: A,B, C & D
Approvals: CSA

Power Requirements: Table A
Voltage: 18-36 Vdc Current: 70mA (50 mA without backlight)
Transducer Power: 18-36 Vdc unregulated (4-20mA Models)
15 Vdc regulated (1-5 V models)

Environment:
Operating Temp. -4° to 140°F (-20° to 60°C)
Storage Temp. -4° to 167° F(-20° to 75°C)
Humidity: 10-100% non-condensing
Sealing: NEMA 4 (IP65) from front
NEMA 12 (IP54) from rear

Input (Table B)
4-20 mA Models

Range: 4-20mA
Linearity: ±0.25% of full scale defelection
Accuracy: 0.5% of full scale deflection
Temperature Drift: 0.005% / °C
Input Impedance: 50W
Overvoltage protect. 15 Vdc
Wirelength: 1500 feet max (22 AWG)

1-5V Models

Range: 1-5 Vdc
Linearty: ±0.25% of full scall deflection
Accuracy: 0.5% of full scall deflection
Temperature Drift: 0.005% / °C
Input Impedance: > 200KW
Overvoltage protect. 15 Vdc
Wire Length: 1500 feet max (22 AWG)

Outputs (optional, Table C & D)
Discrete

Quantity: 2
Type:
Transistor Isolation: optical, 2500 Vax
Voltage: 20 Vdc, max
Current: 20 mA, max

Analog

Quantity: 1 Type: 4-20 mA
Isolation: none

Display
Type: Custom Analog / Digital LCD
Digital display: 4 1 / 2 digit plus sign
Analog display: 101 segment bar graph
Backlight: Optional, 32 lux fiber-optic LED backlight

Mechanical

Material: Flame retardant ABC with RFI shielding
Panel Cutout: 1.77" x 3.62" (92 x 45 mm)
Wiring: 2-part Phoenix, type MC, 3.8 mm pitch

8576B - µGauge
Model 8576B µGauge
back to product categories >


This and other information from AMOT provide product or system options for further investigation by users having technical expertise. Before you select or use any product or system, it is important that you analyze all aspects of your application and review the information concerning the product in the current product catalog. The user, through its own analysis and testing, is responsible for making the final selection of the system and components and assuring that all performance, safety and warning requirements of the applications are met.

©1997-2005 AMOT