I/P Converter

Current to Pressure (I to P) Converters

8064A

8064A Electro/Pneumatic (I/P) Converter

Supply Pressure: 1.3 to 2.1 bar 18 to 30 psi
Input: 4 to 20 mA  
Output: 0.2 to 1 bar 3 to 15 psi
Zero offset adjustment: +40% to -20% of span
Output capacity: 0.16 SCFM 
Output volume 170cc max. recommended
Coil resistance: 185 Ohms 
Vibration: 5 - 100 Hz 4g Lloyds Register requirement for equipment mounted on-engine

See datasheet for complete specifications.

Electro-Pneumatic (I/P) Converter

8064C Electro/Pneumatic (I/P) Converter

Supply pressure: 1.2 to 10 bar 18 to 150 psi
Output: 0.2 to 1 bar 3 to 15 psi
Supply sensitivity: Less than 0.1% span over full supply pressure range
Flow: Max 300N l/min (12 scfm)
Air consumption: <2.5N l/min at 50% signal (0.025 cfm)
Temperature effect: Typically less than 0.035% of span/°C between -40°C to +85°C (-40°F to +185°F)
Response time: 1 sec (from 0 to 90% or 100 to 10% of output pressure into a 0.5 litre load)
Degree of protection: IP66, NEMA 4X (when mounted upright)
Linearity: <0.1% of span
Hysteresis: <0.1% of span

See datasheet for complete specifications.