| Supply pressure: |
1.2 to 10 bar |
18 to 150 psi |
| Output: |
0.2 to 1 bar |
3 to 15 psi |
| Supply sensitivity: |
Less than 0.1% span over full supply pressure range |
| Flow: |
Max 300N l/min (12 scfm) |
| Air consumption: |
<2.5N l/min at 50% signal (0.025 cfm) |
| Temperature effect: |
Typically less than 0.035% of span/°C between -40°C to +85°C (-40°F to +185°F) |
| Response time: |
1 sec (from 0 to 90% or 100 to 10% of output pressure into a 0.5 litre load) |
| Degree of protection: |
IP66, NEMA 4X (when mounted upright) |
| Linearity: |
<0.1% of span |
| Hysteresis: |
<0.1% of span |